Steps to choose Panasonic Ventilating Fans.
- Calculate the capacity of the room
Capacity of room = Width
x Length x Height (Unit : metre)
- Calculate the required air volume
Required air volume (CMH) = Capacity of room x Air change rate
3. Compare the required air volume with the
specification of fans
Example
:
Capacity of room = 3 x 3 x 2.5
= 22.5
Required air volume (CMH) = 22.5 x 6
= 135 CMH
The suitable Ceiling Mount Ventilating fan is FV-24CUT3 (140 CMH)
***Air change rate has details as follows :
Place
A
B
Place
A
B
Hotel
Restaurant, Dancing Room
8
School
Canteen
15
Kitchen
15
Meeting Room
6
Hallway, Restroom
5
Gym
8
Toilet
10
Toilet
12
Cleaning Room
20
Library, Laboratory
6
Drycleaning Room
15
Classroom
6
Hospital
Lobby
10
Cinema
Meeting Room, Aisle
6
Clinic, Patient Diagnosing Room
6
Smoking Room
12
Toilet
5
Toilet
10
Office
6
Projector
20
Canteen, Restaurant
8
Office
6
Kitchen
15
Communication Control Room
6
X-Ray Room
5
Factory
Painting Room
20
Toilet, Boiling Room
10
Electric Generating Room
20
Drycleaning Room
15
Steaming Room
15
Patient Room
10
Office
6
Public
Public Toilet
20
Restaurant
Restaurant
6
House
Kitchen
15
Kitchen
20
Living Room
6
Office Building
Office
6
Photo Room
Darkroom
10
Lobby
10
Chemical Producing Room
more than 20
Meeting Room
12
Showroom
10
Toilet
10

How to Choose Fans?